aboutsummaryrefslogtreecommitdiff
path: root/README.md
blob: 2e5ba838befcf5790825d6bd28d6f7b0b1cee2f2 (plain) (blame)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
# Deckungsanteil Wärmepumpe

Like BWP WPsim, but for every German postcode. Hourly DWD air temperatures 2007–2025
(about 470 stations, nearest station per postcode) drive a simple model:

- Heating load linear from Norm-Heizlast at Norm-Außentemperatur to 0 at the heating limit.
- Heat pumps: Remko LWM 80/110/150 (installation manual) and Panasonic Aquarea generation J
  (WH-MDC05/07/09J3E5) and generation L (WH-WDG05/07/09LE5, service manual heating
  capacity tables) with maximum capacity and COP per outdoor and flow temperature
  (W35/W45/W55), see `web/devices.js`. The bivalence point
  follows from capacity and load; in bivalent-alternativ mode it is a manual switching
  temperature. Load the heat pump cannot cover above it is shown as uncovered. Hours below
  the minimum capacity are counted as cycling (Remko only; Panasonic does not publish it).
- Generic heat pump: capacity equals the load at a manual bivalence point and changes by a
  fixed %/K; COP of the LWM 110 (air) or Carnot-based (ground/water).
- Modes: monovalent (heater rod), bivalent-parallel (optional cut-off temperature),
  bivalent-alternativ. Flow temperature fixed or weather-compensated.
- Inputs in five steps (location, building, heat pump, hot water & PV, costs), then the
  full results; the key figures stay visible above every step and update live.
- Backup fuel: heater rod, natural gas, LPG, oil, pellets or firewood, with amounts in kWh, m³, l, kg or rm.
- Optional hot water and PV, each switched on separately (step 4, results in their own section):
  - Hot water: daily demand charged from 11 to 15 h MEZ at tank temperature + 5 K, with
    priority over heating; the backup heater covers what the heat pump cannot.
  - PV: hourly yield from DWD 10-minute global and diffuse irradiation (nearest solar
    station per year), south, 30° tilt, Hay-Davies transposition, 14 % losses, module
    temperature from the air temperature. Inputs are only kWp and battery kWh (90 % round
    trip, 1 C) and whether surplus is fed in (otherwise curtailed). PV and battery supply
    the heat pump and heater rod only, no household load.
- Results: heat demand, coverage shares, JAZ, electricity, self-consumption, autarky,
  costs; charts and CSV export.

The app is static HTML/JS; all calculations run in the browser.

## Quick start

Requires [uv](https://docs.astral.sh/uv/). The weather data is not part of this
repository. Build it once from the original sources (downloads about 1.9 GB into
`.cache/`, writes about 190 MB to `web/data/`, takes about 30–60 minutes):

```sh
uv run scripts/prep.py
```

uv picks a suitable Python and installs the script's dependencies (numpy, pandas) from the
metadata at the top of `scripts/prep.py`.

Then serve the `web/` directory and open http://127.0.0.1:8765:

```sh
uv run python -m http.server 8765 -d web
```

Re-running `scripts/prep.py` reuses the downloads in `.cache/`; delete that directory to
fetch fresh data (for example after DWD publishes a new year).

## What `scripts/prep.py` does

1. Downloads the station list and hourly air temperature archives (`historical/`) from the
   [DWD Climate Data Center](https://opendata.dwd.de/climate_environment/CDC/observations_germany/climate/hourly/air_temperature/historical/).
2. Keeps years with at most 3 % missing hours and no gap over 72 h (gaps are interpolated)
   and stations with at least 10 such years.
3. Estimates the Norm-Außentemperatur per station as the two-day mean undercut on 10 days
   in 20 years. This is within about 0.5–2.5 K of the DIN/TS 12831-1 values (usually
   warmer); the user can override it.
4. Downloads the 10-minute solar archives from
   [DWD](https://opendata.dwd.de/climate_environment/CDC/observations_germany/climate/10_minutes/solar/historical/),
   sums them to hours (UTC, all six values required) and keeps years with global
   irradiation under the same gap limits; missing hours are filled from the same hour of the
   surrounding days, missing diffuse values with the Erbs correlation. Stations that only
   record sunshine duration are skipped. The PV yield per kWp is computed here and written
   to `web/data/pv/`; each temperature station uses the nearest solar station per year.
5. Downloads [GeoNames postal codes](https://download.geonames.org/export/zip/) and assigns
   each postcode to its nearest station.

## Limitations

- No altitude correction between postcode and station.
- JAZ ignores cycling, circulation pump and tank losses beyond the hot water demand entered,
  so it is on the optimistic side.
- PV orientation is fixed; the battery starts empty every year and is not charged from the grid.
- Device data is full load at nominal conditions; part load, defrost beyond the datasheet
  points and other devices are not modelled. Remko capacities were digitised from the manual's
  diagrams (about ±0.2 kW).
- Not affiliated with BWP, Remko, Panasonic or DWD.

## License and data sources

Code: [MIT](LICENSE).

The generated data is subject to its sources' terms:

- Weather data: Deutscher Wetterdienst (DWD), Climate Data Center, hourly air temperature
  and 10-minute solar irradiation, see the [DWD terms of use](https://opendata.dwd.de/climate_environment/CDC/Terms_of_use.pdf).
  Attribution: "Datenbasis: Deutscher Wetterdienst".
- Postcodes: [GeoNames](https://www.geonames.org/), CC BY 4.0.